R 90 PROTECTION OF STEEL RODS

Classification Report

Regulation: EN 1363-1:2012

Laboratory: Istituto Giordano

Test report: 313123

Average temperature<350°C after 90 minutes

Solution:

  1. Ø inner diam of pipe section 28mm thickness 30mm

  2. Ø inner diam of pipe section 102mm thickness 40mm

  3. Ø outer diam of solution 182mm

 

R 90 protection of steel rods with stone wool pipe setion with concentric fiber PAROC Pro Section 140 AluCoat thickness 70 mm (30+40mm) coated with aluminum foil.

PAROC Pro Section 140 AluCoat has a longitudinal cut to be easily installed on the steel rod. Close pipe section with steel wire.

Technical characteristics PAROC Pro Section 140 AluCoat:

  • density 140kg/m3

  • inner diameter 35 mm (availble also inner diam 28 mm and 42 mm)

  • lenght 1200 mm

  • tota thickness 70 mm

  • thermal conductivity l = 0,034 W/mk (value at 10°C)

  • fire reaction:

    • A1L (uncoated pipe section)

    • A2L- s1, d0 (pipe section coated with aluminum foil);