Classification Report
Regulation: EN 1363-1:2012
Laboratory: Istituto Giordano
Test report: 313123
Average temperature<350°C after 90 minutes
Solution:
Ø inner diam of pipe section 28mm thickness 30mm
Ø inner diam of pipe section 102mm thickness 40mm
Ø outer diam of solution 182mm
R 90 protection of steel rods with stone wool pipe setion with concentric fiber PAROC Pro Section 140 AluCoat thickness 70 mm (30+40mm) coated with aluminum foil.
PAROC Pro Section 140 AluCoat has a longitudinal cut to be easily installed on the steel rod. Close pipe section with steel wire.
Technical characteristics PAROC Pro Section 140 AluCoat:
density 140kg/m3
inner diameter 35 mm (availble also inner diam 28 mm and 42 mm)
lenght 1200 mm
tota thickness 70 mm
thermal conductivity l = 0,034 W/mk (value at 10°C)
fire reaction:
A1L (uncoated pipe section)
A2L- s1, d0 (pipe section coated with aluminum foil);